Most motor circuits are protected by dual-element time-delay fuses or _________.


A) dual-time circuit breakers
B) instantaneous trip circuit breakers
C) nontime delay fuses
D) inverse-time circuit breakers

E) A) and D)
F) All of the above

Correct Answer

verifed

verified

Which NEC table lists the running currents for single-phase ac motors?


A) 430.247
B) 430.248
C) 430.249
D) 430.250

E) C) and D)
F) B) and D)

Correct Answer

verifed

verified

The starting current of a squirrel-cage motor can be determined by multiplying the kVA rating by the_________ rating and then dividing by the applied voltage.


A) nameplate
B) horsepower
C) locked-rotor
D) resistance

E) B) and C)
F) A) and B)

Correct Answer

verifed

verified

B

A 25-horsepower, three-phase induction motor has a nameplate rating of 32 amperes. The nameplate also shows a temperature rise of 30 degrees C. What is the overload size for this motor in amperes?


A) 20
B) 30
C) 40
D) 50

E) B) and C)
F) A) and C)

Correct Answer

verifed

verified

Most common squirrel-cage motors used in industry fall into the design _________classification.


A) A
B) B
C) C
D) D

E) A) and B)
F) B) and D)

Correct Answer

verifed

verified

How does temperature rating impact conductor size selection?

Correct Answer

verifed

verified

Another factor that must be taken into consideration when determining the conductor size is the temperature rating of the devices and terminals. The conductor will be selected and coordinated so as to not exceed the lowest temperature rating of any connected termination, any connected conductor, or any connected device. This means that regardless of the temperature rating of the conductor, the allowable ampacity must be selected from a column that does not exceed the temperature rating of the terminations. The conductors listed in the first column of NEC Table 310.16 have a temperature rating of 60 degrees C (140 degrees F), the conductors in the second column have a rating of 75 degrees C (167 degrees F), and the conductors in the third column have a rating of 90 degrees C (194 degrees F). The temperature ratings of devices such as circuit breakers, fuses, and terminals are found in UL product directories. The temperature rating may be found on the piece of equipment. As a general rule, the temperature rating of devices will not exceed 75 degrees C (167 degrees F).

What is the relationship between the rotor bars of a squirrel-cage motor and the starting current?

Correct Answer

verifed

verified

If the nameplate lists code letters that...

View Answer

A 100-horsepower, three-phase squirrel-cage induction motor is connected to a 240-volt line. A dual-element time- delay fuse is to be used as the short-circuit protective device. What is the correct fuse rating?


A) 300
B) 350
C) 400
D) 450

E) B) and C)
F) B) and D)

Correct Answer

verifed

verified

If a synchronous-type motor is operated at 90 percent power factor, the rated full-load current in the table is to be ____.


A) decreased by 90%
B) decreased by 10%
C) increased by 10%
D) increased by 90%

E) C) and D)
F) A) and D)

Correct Answer

verifed

verified

A 150-horsepower, three-phase squirrel-cage induction motor is connected to 440 volts. The motor nameplate lists the following information: Amps 175 SF 1.25 NEMA code B The conductors are to be copper with type THHN insulation. The short-circuit protective device is to be an inverse- time circuit breaker. The termination temperature rating is not known. Determine the conductor size and overload size.

Correct Answer

verifed

verified

The conductor size is determined from th...

View Answer

What should be done if a dual-element time-delay fuse will not let the motor start?

Correct Answer

verifed

verified

If for some reason this fuse will not pe...

View Answer

The temperature ratings of devices such as circuit breakers, fuses, and terminals are found _________.


A) on the nameplate
B) in the NEC tables
C) in UL product directories
D) through individual testing

E) A) and D)
F) All of the above

Correct Answer

verifed

verified

Two-phase motors that are especially designed for_________ applications use the same rules for determining full-load currents as single-phase motors.


A) high speed-high torque
B) low speed-high torque
C) high speed-low torque
D) low speed-low torque

E) C) and D)
F) B) and D)

Correct Answer

verifed

verified

B

What is included in the NEC motor tables, and how is this information used?

Correct Answer

verifed

verified

The tables list the amount of current th...

View Answer

What percentage of the full-load current of a thermally protected continuous-duty motor of more than one hp can the trip current be, if the full-load current is 15 amperes?


A) 122
B) 140
C) 156
D) 170

E) A) and B)
F) A) and C)

Correct Answer

verifed

verified

A one-horsepower motor will have a full-load current of_________ amperes when connected to 90 volts dc.


A) 6.8
B) 9.5
C) 9.6
D) 12.2

E) B) and C)
F) C) and D)

Correct Answer

verifed

verified

The motor overload size is to be determined by using the current listed _________.


A) on the nameplate
B) in the NEC tables
C) in the UL tables
D) on the stator

E) C) and D)
F) B) and D)

Correct Answer

verifed

verified

The voltages of a two-phase system are_________ degrees out of phase with each other.


A) 90
B) 120
C) 150
D) 180

E) A) and D)
F) None of the above

Correct Answer

verifed

verified

When a two-phase, three-wire system is used, the size of the neutral conductor must be increased by_________ .


A) the square root of two
B) two
C) the square root of three
D) three

E) None of the above
F) A) and B)

Correct Answer

verifed

verified

_________motors are often made to have a leading power factor by overexcitation of the rotor current.


A) Unity
B) Squirrel-cage
C) Wound-rotor
D) Synchronous

E) All of the above
F) A) and C)

Correct Answer

verifed

verified